answersLogoWhite

0


Best Answer

277 volts is the phase to neutral voltage on a 480V 3-phase system. There is really no such thing as 277V 2-phase. Can you convert 277/480V 3-phase utility power to 120/240V single phase? Sure, but it will be expensive for any reasonable amount of power. You will need three Transformers with 480:120 ratios. The primaries are each fed 480V A-B, B-C, and C-A. The three secondaries are connected in what is called a zig-zag configuration. The output will be 120/240V. This is rarely to never done with utility power using transformers, but it is routinely done on generators to obtain single-phase power when only a 3-phase generator is available. The generator must be reconnectable, that is, the three (sometimes six)windings must not be connected internally. One drawback is you can only load such a system to 66% of its rated power. So a 60KW 3-phase generator reconnected in a zig-zag configuration can only supply 40KW of single-phase power. But at least you don't need any transformers! Look at a generator manufacturer's website (Marathon has a good one). They have technical data on these types of arrangements. So while it is theoretically possible, its not really practical unless you are talking about a generator.

User Avatar

Wiki User

15y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

12y ago

Yes, you can but the wattage output rating of the heater will not be reached due to the lower applied voltage. For example if the heater is 5000 watts at 277 volts, the current is I = W/E 5000/277 = 18 amps. The resistance of the heater is R = W/I (squared) = 5000/18 x 18 (324) = 15.43 ohms. Applying 220 volts on the same heater whose resistance is 15.43 ohms results in this new heater wattage rating. W = E (squared)/R = 220 x 220 (48400)/15.43 = 3137 watts. W = watts, I = amperage, R = resistance in ohms and E = voltage.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: How do you obtain 277 volts single phase from a three phase 480?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

How do you calculate 440v phase?

Let's get the terminology correct. A 'phase voltage' is measured across a phase, whereas a line voltage is measured between two lines. So there is no such thing as a 'phase to phase' voltage -it's a line to line voltage (hence the term 'line voltage').


Can you run single phase 230 from one side of 480 volt 3 phase?

No, you will not obtain 230 volts. From a wye connected three phase 480 volt supply, 277 volts can be obtained from one phase leg and the neutral on the wye connection. 480 volts/1.73 (sq. root of 3) = 277 volts.


How do you get single phase 440 from three phase 440?

You Don't. 440volt 3-phase is actually 480 volts, taking a single phase gives 277Volts single phase. To get single phase 440 you would use one leg of three phase 440/760 three phase power.


Is 126 volts three phase?

126 volts sounds very close to a standard home voltage of 120 volts, which is single phase. 208v is a three phase voltage, and is the lowest I have seen. 240 is single phase (usually center tapped, so in your house you have +120, and -120 referenced to the neutral which provides the normal 240 for dryers, stoves, etc.).


How do you get a 220 volt single phase from 380 volt 3phase synchrounos generator?

220 volt single phase from 480 volt 3 phase that one wire taken one phase and second wire connected in earth point. we get 220 v The above answer is incorrect, one phase from a three phase 480 volt system will give you 277 volts to ground. You must use a transformer to get the voltage you need.

Related questions

How do you calculate 440v phase?

Let's get the terminology correct. A 'phase voltage' is measured across a phase, whereas a line voltage is measured between two lines. So there is no such thing as a 'phase to phase' voltage -it's a line to line voltage (hence the term 'line voltage').


What happens if the source of 220 Volts originates from two legs of a 3-phase circuit?

Nothing happens. This is a normal way to obtain a single phase system from a three phase system.


Can you run single phase 230 from one side of 480 volt 3 phase?

No, you will not obtain 230 volts. From a wye connected three phase 480 volt supply, 277 volts can be obtained from one phase leg and the neutral on the wye connection. 480 volts/1.73 (sq. root of 3) = 277 volts.


How do you get single phase 440 from three phase 440?

You Don't. 440volt 3-phase is actually 480 volts, taking a single phase gives 277Volts single phase. To get single phase 440 you would use one leg of three phase 440/760 three phase power.


Well Pump Installation?

form_title=Well Pump Installation form_header=12353 Are you in need of single or three phase power?*= () Single phase () Three phase () Don't Know Do you know the voltage of you power supply?*= () 155 volts () 208 volts () 230 volts () 460 volts () Don't Know () Other


How will a 3 phase panel give you 110 volts and 220 volts?

A three phase panel will not give you 110 and 220 volts. A three phase four wire panel will, but not at these voltages. The nearest voltages will be 120 and 208 volts. The 120 volt is the wye voltage of 208 volts. 208/1.73 = 120 volts. A single phase three wire panel will give you 110 and 220 volts.


Is 380 volts electric motor a single phase or 3 Phase?

It is probably a three phase 50 Hz motor.


Is 126 volts three phase?

126 volts sounds very close to a standard home voltage of 120 volts, which is single phase. 208v is a three phase voltage, and is the lowest I have seen. 240 is single phase (usually center tapped, so in your house you have +120, and -120 referenced to the neutral which provides the normal 240 for dryers, stoves, etc.).


What amperage will a range with a rating of 12.9 kw draw?

This depends on what voltage the range is rated for and if it is single phase or three phase. At 220 volts single phase it is about 60 amps, 240 v single phase , 53 amps and at 480 v three phase about 15 amps.


Three phase voltage in india?

It is 230V single phase and 440V in 3 phase system at 50 Hz.AnswerIf the single-phase voltage is 230 V, then the three-phase voltage must be 400 V, not 440 V. The line voltage is 1.732 times the phase voltage.


How do you obtain a 230 volts single phase supply from a 400 volts three phase four wire supply?

400 volt three phase on a grounded system is 230 volt single phase, with each phase 120 degrees apart. So, if you have a 400 volt, three phase four wire service (grounded service), you can pull one phase off and reference to the neutral for 230 volt service. Note this may not allow 115 volt service, unless there is also a center tap for each phase.


What is the US 3 phase voltage?

A balanced three phase system is composed of three single phase voltages having the same amplitude and frequency but displaced from one another by 120 degrees (1/3 cycle).We know that a single coil (winding) rotating in a magnetic field produces a single phase alternating voltage. Similarly, three phase voltage can be produced by a set of three coils separated from each other by 120 electrical degree. Three phase power is so popular because of following advantages.For a given size of frame, a three phase generator or motor has a bigger output than a single- phase machine.To transmit a given amount of power at a given voltage over a given distance, a three phase transmission line requires less copper than a single phase line.Three phase motors are self starting; single phase motors are not self startingParallel operation of three phase alternators is simpler than that of a single phase alternators.