Incorrectly connecting a multi-phase motor could potentially cause a huge problem. Inside of the cover where the motor leads reside (we call them 'pigtails') is a diagram of the lead connections. They are wired for typically either 230V or 460 Volt AC operation

User Avatar

Wiki User

13y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

10y ago

Answer for USA, Canada and countries running a 60 Hz supply service.

When using a three phase contactor, a three phase overload block must be used. The wiring of the contactor consists of taking L1, L2 and L3 of the supply and connecting it to L1, L2 and L3 of the contactor. The load is connected to T1, T2 and T3 on the bottom of the overload block.

If you are using a three wire control for operating the contactor the contactor must have a N.O. contact on it to seal the contactor in once the contactor coil has been energized.

The overload block has three N.C. contacts, one for each leg of L1, L2 and L3. These three contacts are wires in series to the stop - start circuit.

Years ago on old schematic diagrams these contacts used to be placed on the down stream side of the magnetic starter's coil (between the coil and the neutral). When the overloads tripped the voltage was left on the control circuit which was found to be dangerous for trouble shooting. Now the overload contacts are positioned in the beginning of the start- stop circuit so that when a overload trips, the whole stop - start circuit becomes de energized.

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: How do you connect a 9-wires 3-phase motor?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What is the Max amp rating for 3phase dc motor?

the three phase dc motor never seen yet motor eaither 3phase m/r or dc motor.


Which starter is best for 7.5 hp 3phase motor?

Which starter is best for 7.5 hp 3phase motor?Read more: Which_starter_is_best_for_7.5_hp_3phase_motor


You switched leads on your 3phase motor and it did not reverse?

Then it is not a three phase motor.


How do you convert 3phase 1hp motor into units?

Into units of what?


What size of wire use for 3kw motor 380volts 3phase?

How to calculate a cable size of 3kw motor


Can a 220 volt 3 phase motor be connected to a 208 3phase curcit?

Yes.


Can i run single phase dc motor from 3phase bldc controller. i m using single phase motor in motorcycle and controller from other electric vehicle. if yes please tell me how to connect it?

It is possible to run a DC motor on a 3-phase supply using a full-wave rectifier if the voltage is right.


Can a 415volt 3phase motor run on 525 volt 3 phase?

It is not advisable to run lower voltage motor on a higher voltage.


What is the cable size for 1.5KW 3 phase induction motor?

Sir, what is the cable size for 1.5kw 3phase induction motor 400v?


What is the amperage and kw of a 75hp 380v 3phase 50hz motor...same for 25hp and 1hp?

100


How can you operate a electric motor rated at 400V 3phase 50Hz on a 400V 3phase 60Hz system?

Yes, however, the RPM will increase by 20%, if the motor is connected to a shaft or driving something that can not handle the torque, then you might run to heating issues or performance issues.


How can you operate a electric motor rated at 400V 3phase 50Hz on a 480V 3phase 60Hz system?