answersLogoWhite

0


Best Answer

You need an inverter or a motor-generator set. However, the cost of this will be quite high, and the efficiency will be quite low. Also, the available power will be rather low. The most cost-effective solution is to simply obtain 3 phase 480 volt power from your utility.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

18y ago

first off, the two 110v circuits would have to be from different bus bars in the breaker panel, one from the left bus and one from the right bus. if they are both from the same bus you can't do it. if you count down from the top on one side of the breaker panel, every other single breaker space (they're numbered, 1,3,5,7... or 2,4,6,8...) is on the opposite bus, and the top breaker on each side is on the opposite bus. if you call the busses a and b then top to bottom on the left would be ababab... and top to bottom on the right would be bababa... if the two 110v circuits are from different busses, then the black (hot) wires from the two circuits would have 220v potential between them and the white wires (neutrals) would have no potential between them because they are connected to the same place back in the breaker panel, the neutral bus. if all you want is 220v, then the black wires would be all you need. it is a code violation to do this, however because an electrician or fireman has no way to know that he has to turn off two breakers to kill power to the one 220v device unless the two 110v breakers are together on the same side of the panel (ab or ba) and they are clearly marked on the legend as serving the same device.

This answer is:
User Avatar

User Avatar

Wiki User

17y ago

If you work in an industrial setting and DON'T know how to do this, you should keep your hands off it.
You are not a suitably qualified individual.
* National Electrical Code definition, NFPA 70 2005 Article 100 I: Qualified Person. "One who has skills and knowledge related to the construction and operation of the electrical equipment and installations and has received safety training on the hazards involved."
* Performing any such operation without suitable qualification subjects your employer to action by OSHA.
Read that as: "financial penalty"

This answer is:
User Avatar

User Avatar

Wiki User

14y ago
Answer for USA, Canada and countries running a 60 Hz power supply service.You use a single phase 480 to 240 volt step down transformer. Connect the primary across the 480 volts and your load across the 240 volt side. Make sure that the transformer has a high enough capacity to carry the load with out getting into an overload condition. The proper size fusing of this transformer can be done on the primary side of the transformer which will protect the secondary side load.

<<>>

As you asked this question here the best advice anyone should give you is to call a licensed electrician to install a new 240 volt circuit with the right breakers, wiring and wall outlet for the appliance you want to use.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

This answer is:
User Avatar

User Avatar

Wiki User

15y ago

Is there still 240V 3 phase around? Take 2 legs of the three phase 240V and use them as primary side of a 240 to 120 transformer. This will give you 120V single phase on the secondary side of the transformer. Make sure that you know the load current on the 120V side and size the transformer accordingly.

This answer is:
User Avatar

User Avatar

Wiki User

10y ago

Answer for USA, Canada and countries running a 60 Hz supply service.

To convert 480 volts single phase to 240 volts single phase you will need to use a step down transformer. Any two legs of a three phase system is classed as single phase. The primary side connection will be any two legs of a 480 volt three phase system. H1 to H2 will be 480 volts. On the secondary side of the transformer the connections will be X1 to X2 which will give you the required voltage of 240 volts single phase. Depending on what the secondary side load current draws will govern the size of the transformer.

The formula to calculate the transformer size is KVA = Amps x Volts/1000.

Connect a 2:1 ratio step-down transformer across any two line conductors of the three-phase supply, and the secondary will provide a 240-V single-phase supply. Unless you are qualified to do so, don't do this yourself, because the circuit will require the installation of overcurrent protection devices such as fuses or circuit breakers, in accordance with the relevant regulations, to make the installation safe.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

You cannot. There is only single phase and three phase. Both come from the power company in wire distribution configurations.

I believe in the Eastern united states there are still some two phase systems. If memory serves these systems have voltages that are 90 degrees apart. Sometimes three wires are used to provide two phase service - the two phases and an oversized neutral wire that is used as the return for both phases. Since there is a phase shift involved to get two phases from one, you must have a phase shifting device to accomplish this. It is generally easier to get two/three phase service from your local utility company as opposed to try to generate it yourself.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

You need a transformer with a center-tapped secondary. There will be 240 across the whole secondary, and two 120's (180 degrees from each other) from center-tap to each leg. In this configuration, the center-tap is grounded and used as the neutral. If the original source is grounded at one end, then a 1:1 transformer is essential, because you cannot arbitrarily ground a center-tap, if one exists, when one leg is already grounded.

Often, when 240 split phase is already provided, it is possible that a 240 branch circuit is provided without a neutral. There will still be a ground, per code, but that ground cannot be used as the neutral1. In this case, you will need to run a new branch circuit, providing two hots, one neutral, and one ground.

----------------------------------------------------------------------------------

1Exception being certain "deemed safe" appliances, such as dryers and ranges. You need to consult the applicable code, because I seem to recall that this requirement has been changed in recent history, for new work. However, just to be clear, the exception allows the appliance to use neutral as ground - the grounded conductor in the branch circuit must still be properly insulated, or it can only be used as a ground, not a neutral. Other than these exceptions, neutral and ground must be maintained separately, all the way back to the distribution panel.

This answer is:
User Avatar

User Avatar

Wiki User

12y ago

There is no such thing as a 480/240-V three-phase generator. This is because there is a 1.732 (root 3) relationship between the line and phase voltages. So, the generator is either a 480/277 V machine, or a 415/240 V machine -depending on which of the two voltages you quote is correct. If the latter (more likely), then the 240-V phase voltage is measured between a line terminal and the neutral terminal, and there is no practical way of modifying the generator to give you a 240/120 V supply. You could use a pair of identical 240/120-V Transformers (of appropriate volt ampere rating) to give you this output, by connecting their 240 V windings in parallel, and their 120-V windings in series. I would advise against this, as you would really need to know exactly what you are doing!

This answer is:
User Avatar

User Avatar

Wiki User

9y ago

You can use a phase converter to make a 240V single phase line into 415V 3 phase line. Just use a rotary phase converter. It is cost effective.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: How can you convert single phase 120 volt to 3 phase 480 volt?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

How do you convert 277v to 120v for an outlet?

i think you just have to change the breaker from a 277 to a 120. 277 breakers are usually a 2 pole breaker and 120 is a single pole breaker. NO. 277v is not two poles, it is one pole, one single pole breaker in a 480 volt 3 phase system (typically). If you want 120 volts from a 277 volt source you need a step down transformer 277 volt to 120 volt , or 480/277 to 120/208 .


Can 1 phase be used with 3 phase?

If you have a 208Y/120 volt 3 phase system, you can use any one of the three phases (hot or ungrounded conductor) with the neutral for 120 volt load or you can use any two phases of the three phase for a single phase 208 volt load. If you have a 120/240 volt 3 phase system, you can use any two phases of the three phase for a single phase 240 volt load or you can use either the A phase or C phase with the neutral for a 120 volt load. You can not use the B phase with a neutral (you would have 208 Volts!).


Can you use a 2 pole breaker for a 120 volt single phase circuit?

A single phase circuit uses a 2 pole breaker if the circuit is 120/240 split phase and the load is connected 240. Both legs are hot, so both need to be protected. This is the normal US/Canada configuration.


How do you obtain a 230 volts single phase supply from a 400 volts three phase four wire supply?

400 volt three phase on a grounded system is 230 volt single phase, with each phase 120 degrees apart. So, if you have a 400 volt, three phase four wire service (grounded service), you can pull one phase off and reference to the neutral for 230 volt service. Note this may not allow 115 volt service, unless there is also a center tap for each phase.


How do you convert 120 volts electric fan to 240 volt?

put double power batteries in

Related questions

Does a 2 horsepower rotary converter plug into 120 single phase and convert it to plug in a 3 phase outlet?

All my experience with rotary phase converters have been in converting 240 volt single phase into 240 volt three phase. They all were hard wired into their respective systems, so my answer is no.


What is the ac equivalent of 98v DC?

120 volt single phase rectifies to about 96 volt DC


How do you convert 277v to 120v for an outlet?

i think you just have to change the breaker from a 277 to a 120. 277 breakers are usually a 2 pole breaker and 120 is a single pole breaker. NO. 277v is not two poles, it is one pole, one single pole breaker in a 480 volt 3 phase system (typically). If you want 120 volts from a 277 volt source you need a step down transformer 277 volt to 120 volt , or 480/277 to 120/208 .


How many current needed for the starting of a 5 horse power single phase motor?

120 volt


What is the Largest amperage single phase 120 volt breaker made?

6000amps &lt;&lt;&gt;&gt; The above answer must have big lugs to accommodate 6000 amp capacity wire. In my breaker catalogue the largest 120 volt single pole breaker is 70 amps, 277 volt single pole is 150 amps and 347 volt single pole is 100 amps. The 120 volt single pole breaker occupies two opposed slots because of its length.


How can you get a 240V single-phase power from a 120V 3-phase service?

First of all there is no common three phase 120 volt service. There is in North America a three wire 120/240 volt single phase service. That being said, if you want to change a 120 volt source to 240 volts it must be done with a transformer. Its classification is a step up transformer. The primary side of the transformer H1 - H2 will be connected to the 120 volts. The secondary side of the transformer X1 - X2 will be connected to the 240 volt load. The transformer is sized by the current required by the 240 volt load.


What would the amperage be if its 480 volt 100 amp 3 phase and you convert it to 120 208 volt single phase?

This seems like a question from an electrical course, and is probably best answered by your course materials. It's your test question, not ours, and there won't always be someone to ask the answer of. Earn your diploma.


How do you convert a 125 volt to a 120 volt receptacle?

You tell yourself the 125 volt receptacle is a 120 volt receptacle. They're the same thing.


I have a 460 volt 3 phase feed to our bldg. We had a single phase condition to our bldg and we had quite a few 120 coils on 460 volt 3 phase VFD contactors short out Do not know why help?

Try rewriting your question so that it makes sense.


What may happen if you accidentally select the 10 volt d c range on an analog meter when testing a single phase supply?

If by single phase, you mean 120/240 AC; it could blowup in your hand!


Can you tap off a 3 phase 277volt ac light fixture to power a single phase 120 volt ac recptacle?

NO! The voltages available in the 3-phase system are 480 (if you wire phase to phase) and 277 (if you wire phase to neutral) Don't try it!


Can 1 phase be used with 3 phase?

If you have a 208Y/120 volt 3 phase system, you can use any one of the three phases (hot or ungrounded conductor) with the neutral for 120 volt load or you can use any two phases of the three phase for a single phase 208 volt load. If you have a 120/240 volt 3 phase system, you can use any two phases of the three phase for a single phase 240 volt load or you can use either the A phase or C phase with the neutral for a 120 volt load. You can not use the B phase with a neutral (you would have 208 Volts!).