answersLogoWhite

0


Best Answer

All three phase four wire systems have the ability to produce a voltage to ground or neutral. Take any phase voltage be it primary or secondary and divide it by the sq. root of 3 which equals (1.73) and you will obtain the phase to ground or neutral voltage. The ground and neutral should be of the same potential and when talking about electrical installations these two words get interchanged quite often. Some three phase secondary voltages are 208, 480 and 600 volts. Electricians will talk about voltages of 120/208, 277/480 and 347/600. The first number is the phase to neutral voltage and the second number is the phase to phase voltage.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

14y ago

A 480 volt 3-phase power service is common in factories in USA and other countries which use 60 Hz ac electrical services. If you use the 480 volt service lines in the 'star' or 'Y' configuration you will have a central neutral point to connect a neutral line. You can then get a 277 volt single phase service by using one of the three phase lines along with that neutral.

This answer is:
User Avatar

User Avatar

Wiki User

16y ago

480v is the line to line voltage on some 3 phase systems.

277v is the voltage from any of these lines to neutral.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: How do you get 277 volts from a 480 volt line?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

Is 277 volt one hot wire?

No, 277 volts is the line to neutral of a 480 volt wye three phase system. L1- N, L2 - N and L3 - N will give you 277 volts. L1 to L2. L2 to L3 and L3 to L1 will give you 480 volts.


What voltage reading would you get from a 277 480 volt system?

From a three phase four wire distribution system the voltages would be as follows. From L1 to N - 277 volts. From L2 to N - 277 volts. From L3 to N - 277 volts. From L1 to L2 - 480 volts. From L2 to L3 - 480 volts. From L3 to L1 -480 volts.


Wiring diagram to convert a 3 phase 480 volt generator to 277 volt?

You should not need a wiring diagram. If the generator has a star point (wye) connection then the phase voltage to ground (star point) is 277 volts. 480/1.73 = 277.


Can you run single phase 230 from one side of 480 volt 3 phase?

No, you will not obtain 230 volts. From a wye connected three phase 480 volt supply, 277 volts can be obtained from one phase leg and the neutral on the wye connection. 480 volts/1.73 (sq. root of 3) = 277 volts.


Can you connect a 277V ballast to 208V line service?

No. A 277 volt ballast needs the correct voltage to operate. The 277 voltage is derived from the star point voltage of a 480 volt three phase system (277/480). The 208 voltage is a three phase line voltage whose star-point voltage is 120 volts (120/208).


What is a 277 volt fluorescent fixture?

A 277 volt lighting fixture is one that is usually used in an industrial application. The reason for this is the voltage rating. A voltage potential of 277 volts is the voltage to neutral (ground) of a three phase four wire 480 volt distribution system. 480 volts / 1.73 = 277 volts. Rather than having to add a transformer to the system to provide 120 volts for lighting, manufactures produced a ballast for fluorescent fixtures that operates on the 227 volt potential.


How do you wire a 277 volt heater from 480 volt box?

Answer for USA, Canada and countries running a 60 Hertz supply service.The 277 volt heater can be wired to a single pole breaker in a 3 phase 4 wire 480 volt distribution panel. The breaker should be sized to the amperage draw of the heater. 277 volts is the star point (wye) voltage of a 480 3 phase system. 480 / 1.73 = 277 volts. The third answer is not correct, two phase legs of a 480 volt system will give you 480 volts. It is the phase leg to ground (neutral) that gives you the 277 volts.A 277 Volt heater or device may not be wired to a 480 Volt circuit or box. A 277 Volt device may only be wired to a circuit rated for 277V/480V equipment.2 legs of 480 volts will give you 277. But since you don't know the answer you probably shouldn't be doing it! Please don't kill yourself, hire a licensed electrician.Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energizedIF YOU ARE NOT REALLY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.


What is the voltage of a 3 phase 4 wire 277 volt lighting circuit?

The voltage of 277 volts is the wye of a three phase 480 volt system. Just as the voltage of 347 is the wye voltage of a three phase 600 volt system. To obtain these voltages for any three phase system, take the three phase voltage and divide it by 1.73. 480/1.73 = 277 volts, 600/1.73 = 347 volts.


Can you get 110 volts from 277volts?

The voltage of 277 is the wye connection of a 480 volt three phase supply. The only way to reduce 277 to 120 volts is with a step down transformer.


Can a 277 unit heater be supplied with 240 volts?

Absolutely not!! 277 volts is developed from a 480 volt power supply employing 1 conductor and a neutral. 240 volt power comprises two hot conductors and NO neutral.


Can you get 120 volts from a 480 volts 3 phase Y generator?

NO, the 480 Volts Y -- is 4 wire system, with three wires which are hot legs @ 480 volts between each three hot legs. A mid tap is a neutral leg (ground) the white wire. Which gives 277 volts between it and any of the three hot legs. so a 4wire 480 volt Y system. Gives 480 /277 volts.


How to wire 277 volt lighting?

A voltage of 277 is the line to neutral voltage of a 480 volt wye three phase system. L1- N, L2 - N and L3 - N will give you 277 volts. L1 to L2. L2 to L3 and L3 to L1 will give you 480 volts. Wiring of three phase equipment should be in the domain of qualified journeyman electrician or apprentices under the supervision of a qualified journeyman electrician.