If the generator is a 12 lead reconnectable, you can use something called a zig-zag connection.
Check the link below. It is an installation manual for a Marathon generator. Zig-zag connections are shown on page 8. For a home, you would use the low zig-zag connection for 120/240V (in the US). One caveat: you can only load a zig-zag single-phase connected generator to a maximum of 66% of its rated load. So, a 15kW 3-phase generator would only provide 10kW single-phase power. If this doesn't quite make sense, hire a pro!
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS. If you do this work yourself, always turn off the power at the breaker box/fuse panel BEFORE you attempt to do any work AND always use a meter or voltage indicator
to insure the circuit is, in fact, de-energized.
Three phase output means three single phase outputs, so to "convert" three phase output to single phase, simply use just one phase or two phases depending on what voltage is supplied and what voltage you want. For example, a 120/208V three phase generator will give you 120V single phase-to-neutral or 208V single-phase (line-to-line) using one or two phases respectively.
You cannot convert a 3 phase generator to single phase. If the generator is a 4 wire generator you can connect a single phase load between the neutral wire and any one phase wire. Just make sure the voltage of the generator and the load are the same.
If you have what is known as a 12 lead generator. You can change the voltage and phase to what you need. But if it is a four wire 3 phase unit it cannot be changed. As the other poster stated.
A single phase generator can not be converted to run a three phase house. Selective loads could be picked up from one of the three phase legs but the balancing of the loads and switching would be very hard for a home owner to achieve. This is one job that would be better suited for an electrician to look after.
You can take three separate single-phase circuits from a 3-ph generator. Just use one of the live wires plus the neutral to make a single-phase supply. <<>> A three phase generator does not have to be converted to single phase. In electrical terminology any two legs from a three phase system are classed as single phase. No matter what voltage the generator is producing, L1 - L2, L2 - L3, L3 - L1 are classed as single phase legs along with L1 - N, L2 - N, L3 - N. If the generator output voltage is not the voltage that you are looking for use any two legs of the generators output voltage and use a transformer to obtain the voltage that you need.
It's an electrical generator converting mechanical power into electrical power. The electrical power comes out in the form of single-phase alternating current.
yes of course provided you satisfy the principle of generator a coil has to be rotated in a magnetic field. make arrangements to produce a magnetic field in either stator or rotor and also to draw produces current from the lets
Terminology gets misapplied but a 3-phase converter produces a 3 phase supply from a single phase supply. The only proviso is that generator, converter and motor are all suitably rated and compatible.
Houses generally run on single phase power. It would not make sense to convert single phase to three phase to run a house. Please restate the question.
There is no such thing as a two phase load any more. Any two legs from a three phase system are classed as single phase. If this single phase load is connected across the generator it will induce an imbalance in the output voltages of the generator. This is one reason that single phase loads on a three phase generator should be shifted around to find the best possible balance.
You can take three separate single-phase circuits from a 3-ph generator. Just use one of the live wires plus the neutral to make a single-phase supply. <<>> A three phase generator does not have to be converted to single phase. In electrical terminology any two legs from a three phase system are classed as single phase. No matter what voltage the generator is producing, L1 - L2, L2 - L3, L3 - L1 are classed as single phase legs along with L1 - N, L2 - N, L3 - N. If the generator output voltage is not the voltage that you are looking for use any two legs of the generators output voltage and use a transformer to obtain the voltage that you need.
To answer this question a voltage must be given to find the current output. Also whether the generator is three phase or single phase.
If the windings are brought out separately, so they may be connected together in different ways (they are called "reconnectable" windings), then three-phase generators can be reconfigured for single-phase output by means of a "zig-zag" connection. Many connection diagrams for this configuration are available online. One drawback for this method is the output power is reduced to approximately 66% of the three-phase rating.
The formula you are looking for is , A = kva x 1000/Volts.
If the elevator has a single-phase motor, the diesel generator can also be single phase provided the voltage and VA ratings are compatible.
The winding design of the motor will not economically allow this to work. You would have to drive a 3 phase generator to supply it.
how reversing an ac single phase induction motor to wark as induction generator
We can convert a 3 phase ac motor into generator by changing phase sequence of the ac input cable of that motor
It's an electrical generator converting mechanical power into electrical power. The electrical power comes out in the form of single-phase alternating current.
The type of backup generator should match the type of utility service you receive. If your utility power is single-phase (almost all residences in the US are), then yes, your generator should be single-phase as well.
yes of course provided you satisfy the principle of generator a coil has to be rotated in a magnetic field. make arrangements to produce a magnetic field in either stator or rotor and also to draw produces current from the lets