75 HP = 55 KW

55 = 31/2 x 0.220 x I x cos φ = 31/2 x 0.220 x 0.8 x I

I = 55/(31/2 x 0.220 x 0.8) = 180,42 A

3 x 70 mm2 is the size of cable for 75 HP 220 Volts 3 phase motor

User Avatar

Wiki User

14y ago
This answer is:
User Avatar
User Avatar

Fredrick Langat

Lvl 1
7mo ago
Very essential
More answers
User Avatar

Wiki User

11y ago

Have to know what voltage the motor is connected to.

70 mm2 per line, for 134 A and 400V.

Answer for USA, Canada and countries running a 60 Hz supply service.

The formula for amperage when horsepower is shown is,

I = HP x 746/1.73 x E x %Eff. x pf = 75000/1.73 x 400 x .90 x .90 = 75000/561 = 133 amps.

Motor cables have to be rated at 125% of the motors full load amps. 133 x 125% = 166 amps.

A # 2/0 copper wire with an insulation factor of 75 or 90 degrees C is rated at 175 and 185 amps respectively.

If the motor is over a large distance from the supply distribution go to a 3/0 conductor which is one size larger. This will overcome any voltage drop that may occur.

This answer is:
User Avatar

User Avatar

Wiki User

10y ago

The size of the wire would depend on the current drawn, and that depends on the voltage it is designed to work at. A motor that size could be 415 v or a higher voltage.

A 75 kW motor would need a 100 kVA supply and at 415 v that would be 140 amps, requiring a wire size of #0 or 50 mm2 cross section.

At a higher voltage the current would be less and the wire size would be smaller. At 11 kV the current would be only 5.3 amps, requiring wire of only 1.0 mm2 cross-section.

This answer is:
User Avatar

User Avatar

Wiki User

11y ago

No . . . that is because you did not specify the voltage.

This answer is:
User Avatar

User Avatar

Wiki User

10y ago

The cable size feeding 75hp-3phase motor is 16mm square in measurement.

This answer is:
User Avatar

User Avatar

Wiki User

11y ago

150x4

This answer is:
User Avatar

User Avatar

Wiki User

11y ago

240mm sq

This answer is:
User Avatar

User Avatar

Anonymous

Lvl 1
4y ago

380

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What will be the size of cable for 75 HP 220 Volts 3 phase motor?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

What is the cable size for a 168 kilowatt 3 phase motor?

First of all find out what voltage the motor is designed to work on.


What is the cable size for 600V 3 phase ac motor?

you need the current of motor or the KW/HP rating


What is the cable size of 110 KW motor?

The cable size depends on a few factors, such as the supply voltage, the method of starting the motor, (direct-on-line, or star delta) and the length of cable required to compensate for voltage drop. Also, if the cable is copper or aluminum.110 kW motor has a rated current of 200 amps at 415 volts, so the correct copper cable size would have a cross-sectional area of 75 square mm., if the motor is started direct-on-line.At 660 volts, the rated current would be 118 volts and the cable size would be 35 square mm.


Are all large motors three-phase?

Yes, most large motors are three phase. Usually single phase motors only go up to 10 HP. Larger than this and the wire size and contactors used to control the motors becomes extreme. For example a single phase 10 HP motor on 115 volts draws 100 amps. The same single phase motor on 230 volts draws 50 amps. The same 10 HP motor on three phase system draws the following amperage; 230 volts is a 28 amp draw, 460 volts is a 14 amp draw and 575 volts is a 11 amp draw. As you can see the higher the voltage becomes, the smaller the wire feeder size is needed and much smaller size contactor can be used to control the motor.


What is the cable size for 7.5 kw 3 phase motor?

Assuming it is a 400 V three-phase motor, the phase current is 11 amps, or more if the power factor is less than 1.0 (or the supply voltage is different). If it is a 400 V motor the cable should be capable of carrying 16 amps, so a 2.5 mm-sq 4-core cable is needed.

Related questions

What is the cable size for 1.5KW 3 phase induction motor?

Sir, what is the cable size for 1.5kw 3phase induction motor 400v?


What is the cable size for a 168 kilowatt 3 phase motor?

First of all find out what voltage the motor is designed to work on.


What is the cable size for 600V 3 phase ac motor?

you need the current of motor or the KW/HP rating


Computation of three phase motor 230 volts 20 hp in what size of wire?

The supply is probably 400 v three-phase with 230 v between each live and neutral. On this assumption the current is 49 amps and the copper cable size is 16 mm2 for a run of up to 30 metres.


Are all large motors three-phase?

Yes, most large motors are three phase. Usually single phase motors only go up to 10 HP. Larger than this and the wire size and contactors used to control the motors becomes extreme. For example a single phase 10 HP motor on 115 volts draws 100 amps. The same single phase motor on 230 volts draws 50 amps. The same 10 HP motor on three phase system draws the following amperage; 230 volts is a 28 amp draw, 460 volts is a 14 amp draw and 575 volts is a 11 amp draw. As you can see the higher the voltage becomes, the smaller the wire feeder size is needed and much smaller size contactor can be used to control the motor.


What is the cable size of 110 KW motor?

The cable size depends on a few factors, such as the supply voltage, the method of starting the motor, (direct-on-line, or star delta) and the length of cable required to compensate for voltage drop. Also, if the cable is copper or aluminum.110 kW motor has a rated current of 200 amps at 415 volts, so the correct copper cable size would have a cross-sectional area of 75 square mm., if the motor is started direct-on-line.At 660 volts, the rated current would be 118 volts and the cable size would be 35 square mm.


What is the cable size for 7.5 kw 3 phase motor?

Assuming it is a 400 V three-phase motor, the phase current is 11 amps, or more if the power factor is less than 1.0 (or the supply voltage is different). If it is a 400 V motor the cable should be capable of carrying 16 amps, so a 2.5 mm-sq 4-core cable is needed.


What is the size of XL PE cable for 380 Volts in 125 KW motor?

If it's a 380 v 3-phase supply, the current is up to 300 amps which could be supplied over a short distance by XLPE cable with 70 sq. mm cross-section conductors.


What is the start up amps on a 200 hp 3 phase 480 volt motor?

i have 200 hp motor what i need cable size in 100 feet distance


What cable size to use for a 1 kw motor for a 400v 50 hz 3 phase supply?

3 core 35 sq mm alu. Or 3 core 25 sq mm cup.


What size breaker is used for a 3 horse power motor with 3 phase 208 volts?

I would go with 20 amp 3 pole 15 amp will also do


What is the cable size for a 26kw induction motor 50metre run for cable 415v?

Wire sizing is determined by the amount of amperage that the connected device draws. Look on the nameplate of the motor and state the amperage. Then the question can be answered.