What size wire for 400 amp 480 volt service?

Updated: 9/17/2019
User Avatar

Wiki User

11y ago

Want this question answered?

Be notified when an answer is posted

Add your answer:

Earn +20 pts
Q: What size wire for 400 amp 480 volt service?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What size wire needed for 200 amp service 400 feet away direct buried single phase 240 volt 3 wire?

Assuming you are working with 240v, you need 4/0 copper conductors.


How do you obtain a 230 volts single phase supply from a 400 volts three phase four wire supply?

400 volt three phase on a grounded system is 230 volt single phase, with each phase 120 degrees apart. So, if you have a 400 volt, three phase four wire service (grounded service), you can pull one phase off and reference to the neutral for 230 volt service. Note this may not allow 115 volt service, unless there is also a center tap for each phase.


What is the wire size needed to feed a 400 amp service with parallel copper?

It depends on the length of the run


What wire size for 400 amp service neutral size?

You need to look at the regulations that apply in your country. If in doubt, use a neutral wire of the same size as the live wire or wires.


What size wire do you need to run for 30 amp service to travel trailer 400 feet single phase 110 volt?

Presuming that you would like the least expensive installation, the following is calculated on overhead aluminum wire. The wire size needed to hold the voltage drop to 3% would be 3/0 MCM. If the installation could be run on 240 volts then the wire size can be reduced to #2.


What size service cable is required for 120 volt 150 amp direct bury 400 feet single phase?

A 1000 MCM copper conductor will limit the voltage drop to 3% or less when supplying 150 amps for 400 feet on a 120 volt system.


What size wire is needed for 400 amp 480 volt service?

A 500 MCM wire with an insulation factor of 90 degrees C is rated at 430. Most 400 amp services will use parallel wires on each leg to feed the circuit. A 3/0 wire with an insulation factor of 75 and 90 degrees C is rated at 200 and 225 amps respectively. The insulation rating of these conductors will be 600 volts.


Can you run 500mcm to feed 480 volt 400 amp service?

500 mcm (or 500kcmil) conductors are used for 400 amp 480v single phase or 3 phase systems. The wire AND THE TERMINALS must be rated for 90o Celsius.


What size conduit and aluminum wire for a 400 foot run on a 120 240 volt system?

The key parameter in sizing wire is the current requirement. Once you know that you can look up value in a wire gauge table. The length of the run is important for longer runs because of the resistance of the wire itself. Aluminum wire requires a larger diameter than copper for the same current. Once you calculate the wire size you can then size the conduit.


What size wire for a 4000 amp service?

Generators are rated in volt-amps (va) and may also have a wattage rating. In most practical applications volt-amps and watts are the same. At 240v single phase, 400 amps is 96000 volt-amps, or 96kva. I would be looking for a 100 kva generator. This is a large generator if you are considering it for your home. In most situations you identify critical circuits and place only these on the generator through a transfer switch. This allows for a much smaller generator.


What size service conductors do you need for a single phase 600 amp commercial panel?

The size of wire for service entrance conductors for a 400 amp 3 phase service could be 500 MCM copper. This is very large size wire and difficult to bend and shape, to connect to terminals in the main disconnect and distribution panel. This problem is solved by using parallel conductors or on higher ampacities triple conductors. Using parallel conductors the wire size would be three ought (3/0) copper.


What size wire to run 400 ft from main panel need 60 amps?

Use AWG # 4 copper and you will have a 2.6% voltage drop which is acceptible.