The grounding wire is not intended to be a load-carrying conductor in ordinary use, but rather a SAFETY conductor. Grounding wires are often "one size smaller" than the associated load conductors in the same cable.
GAUGE IS THICKNESS THE SMALLER THE # THE THICKER 2- THICK 22- THIN
NO, 10ga has a max of 30 amp, you need 8ga, you should get 8/3wgr, That is 4 wires 2-hot, 1- neutral,1-ground, some appliance's have a ground strap so if the wire only has 3 then you can omit the neutral. But new code is, if installing new wire, must have neutral and ground. Old style- 2-hot,1- neutral. New- 2-hot, 1- neutral,1-ground.
The wire size used in a service entrance distribution panel is governed by the size of the services over current device. The larger the service, the larger the fault current could be, the larger the ground wire to carry the fault current to ground. If the largest service conductor carries 100 amps use a #8, 200 amps - #6, 400 amps - #3, 600 amps - #1, 800 amps - 1/0 and over 800 amps - 2/0 for the ground wire. <<>> Golden Valley Electric Assoc. in Alaska requires #4AWG copper wire for a ground from the breaker box to earth ground rod. The same goes from the service entrance panel on the pole.
yes, it will in theory work, however it is a NEC violation to paralell wires smaller than 1/0, code section 310.10H.
#6 should be fine...Canadian Code anyway....
GAUGE IS THICKNESS THE SMALLER THE # THE THICKER 2- THICK 22- THIN
You need 2 ground rods of 8' in length. One under the meter base and another one 6' to either side of the meter base. Drive them into the ground with just enough sticking up to connect the ground wire.
the smaller the wire the less amps it will send to you amplifier.
# 10 bare copper.
NO. Just ground the amp to the chassis try to make ground short as possable about 12 inches is plenty. BE SURE GROUND WIRE IS THE SAME GAGE AS THE POWER WIRE. If its an 8 ga. + then use 8 ga. for the ground.
A 40 amp breaker is used in conjunction with AWG # 8 copper wire. The black and red wires are connected to the breaker. The ground wire is connected to the ground bar and the white wire is connected to the neutral bar.
No, using the AWG system of measuring wire sizes the smaller the wire numbers go the larger the wire size becomes. Hence the number 14 is smaller that the number 16 so it is largest in size of the two wires.
Ground is sized based on the size of the feeder wire and not the amps of the service! However, for a 600 amp service 1500MCM copper wire is one option (NEC 310.16) ;therefor, ground wire is 3/O copper (NEC 250.66) or another option is a two sets of 350 MCM copper wire then a #2 copper (since the biggest feeder wire is 350MCM).
2/8 is smaller and 2/8 is 1/4
#8 copper
#8 would be fine if you ground each panel separately to the ground rod
12-2 can easily support a 220V 1.5 HP pump out to 200Ft. However you may need a separate #8 ground wire in some states.